Aerosense Mack Magnehelic Gauge SINGAPORE - Enviro Tech Industrial Produccts Delhi India
AEROSENSE DP Gauge
AEROSENSE DP Gauge - Analog
AEROSENSE DP Gauges are extensively used for measuring the differential pressure in pharma clean rooms, HVAC applications, pharmaceutical machinery,Pass Box,etc.
Other Information
- Pay Mode Terms: T/T (Bank Transfer)
Aerosense Differential Pressure Indicator
Aerosense Differential Pressure Indicator is demanded for its impeccable qualities and features. It is extensively demanded in the applications areas where HVAC systems are installed to resolve the problem of humidity & temperature control. It is suitable for energy optimization and therefore widely used for the measurement of HVAC duct pressure. Along with the pr??cised operations it has integrated high speed differential pressure sensor that provide accurate results in a significant manner.
Integrated red LED seven segment display
Differential pressure sensor
Stainless steel at the back
Other Information
- Pay Mode Terms: T/T (Bank Transfer)
Aerosense Differential Pressure Switch
The series of pressure switches Aerosense Differential Pressure Switch is the most updated one.Generally, they are applied in the fan, blower and filter monitoring as well as to measure the pressure and flow of gases & liquids in different industries. Enabled with the effective mechanism these switches have high-tech features & specifications such as selectable switching point adjustment and measurement unit facility in PA.Several additional accessories are also provided for the ease of users that primarily include metallic duct connectors,plastic dust connectors, and fixing screws.
Features:
Pressure and flow monitoring
Two fixing screws
Metallic duct connectors
Aerosense Differential Pressure Gauge
Backed by years of experience of this domain, we present clients with the premium quality of Aerosense Differential Pressure Gage. Used for measurement of differential pressure, the pressure gauge is manufactured by using latest technology. In order to ensure high standards of quality, the Aerosense differential pressure gauge is procured from trusted vendors.
- Excellent measurement accuracy
- Easy to use
- Requires less maintenance
Other Information
- Pay Mode Terms: T/T (Bank Transfer)
Aerosense Differential Pressure Cum Flow Transmitter
Aerosense Differential Pressure cum Flow Transmitter is technically engineered type of flow transmitter that is especially used in HVAC/R industry to control the flow, velocity and static of air pressure. Apart from measuring the flow of air control, this type of transmitter is used in the other major applications such as VAV domain and air flow monitoring across centrifugal fans & blowers. It supports low power consumption as well as enabled with the zero point calibration system.
VAV applications
Minimum resistance
Piezo resistive
Other Information
- Pay Mode Terms: T/T (Bank Transfer)
Differential Pressure Gauge
Differential Pressure Gauge
CE approved Differential Pressure Gage with adjustable bookmarks feature indicates Positive, Negative or Differential pressure.
Applications:
- Filter monitoring
- Blower vacuum monitoring
- Fan pressure indication
- Duct, room or building pressures
- Clean room positive pressure indication
Aerosense Differential Pressure Switch Model PS 200
Aerosense Differential Pressure Switch Model PS 200
Series PS Differential Pressure Switch With dual scale field adjustable Set Point Knob
The Series PS Differential Pressure Switch is designed for pressure, vacuum and differential pressure. The dual scaled adjustment knob allows changes to the switching pressure to be made without a pressure gage. The PS is available in settings from 20 Pa to 4500 Pa. The compact size, adjustment knob and low cost make the PS the perfect choice for HVAC applications.
Product Applications:
Fan, Blower and filter monitoring
Pressure and Flow monitoring
Valve and damper monitoring
Service: Air & non aggressive gases
Material: ABS
Electrical Connection: 3 Screw terminal
Cable Entry: M16
Pressure Connection: Male 0 5 MM
Weight: 150 gms
Operation Temperature: -20 to 60° C
Storage Temperature: -40 to 85° C
Maximum Pressure: 50 kPA
IP Protection: IP54
2 Fixing Screws
2 Plastic duct connectors
2 m tube 0 4/7 mm
Metallic duct connectors
- INTRODUCTIONS
- TECHNICAL DATA
- OPTIONAL ACCESSORIES
- MODEL SUMMARY
Model Code |
Pressure range |
Switching difference |
Accuracy of Switching point Low limit typ. |
Electrical rating resistive load |
Accuracy of Switching Point High limit typ. |
Electrical ratind inductive load |
PS200 |
20. .200 pa |
10 pa |
20 Pa±5 Pa |
200 Pa±20Pa |
01A/250VAC |
Aerosense Differential Pressure Switch Model PS 300
Aerosense Differential Pressure Switch Model PS 300
Series PS Differential Pressure Switch With dual scale field adjustable Set Point Knob
The Series PS Differential Pressure Switch is designed for pressure, vacuum and differential pressure. The dual scaled adjustment knob allows changes to the switching pressure to be made without a pressure gage. The PS is available in settings from 20 Pa to 4500 Pa. The compact size, adjustment knob and low cost make the PS the perfect choice for HVAC applications.
Product Applications:
Fan, Blower and filter monitoring
Pressure and Flow monitoring
Valve and damper monitoring
Service: Air & non aggressive gases
Material: ABS
Electrical Connection: 3 Screw terminal
Cable Entry: M16
Pressure Connection: Male 0 5 MM
Weight: 150 gms
Operation Temperature: -20 to 60° C
Storage Temperature: -40 to 85° C
Maximum Pressure: 50 kPA
IP Protection: IP54
2 Fixing Screws
2 Plastic duct connectors
2 m tube 0 4/7 mm
Metallic duct connectors
- INTRODUCTIONS
- TECHNICAL DATA
- OPTIONAL ACCESSORIES
- MODEL SUMMARY
Model Code |
Pressure range |
Switching difference |
Accuracy of Switching point Low limit typ. |
Electrical rating resistive load |
Accuracy of Switching Point High limit typ. |
Electrical ratind inductive load |
PS300 |
30. .300 pa |
20 pa |
30 Pa±5 Pa |
300 Pa±30Pa |
03A/250VAC |
2A/250VAC |
Aerosense Differential Pressure Switch Model PS 500
Aerosense Differential Pressure Switch Model PS 500
Series PS Differential Pressure Switch With Dual Scale Field Adjustable Set Point Knob
The Series PS Differential Pressure Switch is Designed For Pressure, Vacuum and Differential Pressure. The Dual Scaled Adjustment knob allows changes to the switching pressure to be made without a pressure gage. The PS is available in settings from 20 Pa to 4500 Pa. The compact size, adjustment knob and low cost make the PS the perfect choice for HVAC applications.
Product Applications:
Fan, Blower and filter monitoring
Pressure and Flow monitoring
Valve and damper monitoring
Service: Air & non aggressive gases
Material: ABS
Electrical Connection: 3 Screw terminal
Cable Entry: M16
Pressure Connection: Male 0 5 MM
Weight: 150 gms
Operation Temperature: -20 to 60° C
Storage Temperature: -40 to 85° C
Maximum Pressure: 50 kPA
IP Protection: IP54
2 Fixing Screws
2 Plastic duct connectors
2 m tube 0 4/7 mm
Metallic duct connectors
- INTRODUCTIONS
- TECHNICAL DATA
- OPTIONAL ACCESSORIES
- MODEL SUMMARY
Model Code |
Pressure range |
Switching difference |
Accuracy of Switching point Low limit typ. |
Electrical rating resistive load |
Accuracy of Switching Point High limit typ. |
Electrical ratind inductive load |
PS500 |
30. .500 pa |
20 pa |
30 Pa±5 Pa |
500 Pa±30Pa |
03A/250VAC |
2A/250VAC |
Aerosense Differential Pressure Switch Model PS 600
Aerosense Differential Pressure Switch Model PS 600
Series PS Differential Pressure Switch With Dual Scale Field Adjustable Set Point Knob
The Series PS Differential Pressure Switch is Designed For Pressure, Vacuum and Differential Pressure. The Dual Scaled Adjustment knob allows changes to the switching pressure to be made without a pressure gage. The PS is available in settings from 20 Pa to 4500 Pa. The compact size, adjustment knob and low cost make the PS the perfect choice for HVAC applications.
Product Applications:
Fan, Blower and filter monitoring
Pressure and Flow monitoring
Valve and damper monitoring
Service: Air & non aggressive gases
Material: ABS
Electrical Connection: 3 Screw terminal
Cable Entry: M16
Pressure Connection: Male 0 5 MM
Weight: 150 gms
Operation Temperature: -20 to 60° C
Storage Temperature: -40 to 85° C
Maximum Pressure: 50 kPA
IP Protection: IP54
2 Fixing Screws
2 Plastic duct connectors
2 m tube 0 4/7 mm
Metallic duct connectors
- INTRODUCTIONS
- TECHNICAL DATA
- OPTIONAL ACCESSORIES
- MODEL SUMMARY
Model Code |
Pressure range |
Switching difference |
Accuracy of Switching point Low limit typ. |
Electrical rating resistive load |
Accuracy of Switching Point High limit typ. |
Electrical ratind inductive load |
PS600 |
40. .600 pa |
30 pa |
40 Pa±5 Pa |
600 Pa±30Pa |
03A/250VAC |
2A/250VAC |
Aerosense Differential Pressure Switch Model PS 1500
Aerosense Differential Pressure Switch Model PS 1500
Series PS Differential Pressure Switch With Dual Scale Field Adjustable Set Point Knob
The Series PS Differential Pressure Switch is Designed For Pressure, Vacuum and Differential Pressure. The Dual Scaled Adjustment knob allows changes to the switching pressure to be made without a pressure gage. The PS is available in settings from 20 Pa to 4500 Pa. The compact size, adjustment knob and low cost make the PS the perfect choice for HVAC applications.
Product Applications:
Fan, Blower and filter monitoring
Pressure and Flow monitoring
Valve and damper monitoring
Service: Air & non aggressive gases
Material: ABS
Electrical Connection: 3 Screw terminal
Cable Entry: M16
Pressure Connection: Male 0 5 MM
Weight: 150 gms
Operation Temperature: -20 to 60° C
Storage Temperature: -40 to 85° C
Maximum Pressure: 50 kPA
IP Protection: IP54
2 Fixing Screws
2 Plastic duct connectors
2 m tube 0 4/7 mm
Metallic duct connectors
- INTRODUCTIONS
- TECHNICAL DATA
- OPTIONAL ACCESSORIES
- MODEL SUMMARY
Model Code |
Pressure range |
Switching difference |
Accuracy of Switching point Low limit typ. |
Electrical rating resistive load |
Accuracy of Switching Point High limit typ. |
Electrical ratind inductive load |
PS1500 |
100...1500 pa |
80 pa |
100 Pa±1OPa |
1500 Pa±150Pa |
03A/250VAC |
2A1250VAC |
Aerosense Differential Pressure Switch Model PS 4500
Aerosense Differential Pressure Switch Model PS 4500
Series PS Differential Pressure Switch With Dual Scale Field Adjustable Set Point Knob
The Series PS Differential Pressure Switch is Designed For Pressure, Vacuum and Differential Pressure. The Dual Scaled Adjustment knob allows changes to the switching pressure to be made without a pressure gage. The PS is available in settings from 20 Pa to 4500 Pa. The compact size, adjustment knob and low cost make the PS the perfect choice for HVAC applications.
Product Applications:
Fan, Blower and filter monitoring
Pressure and Flow monitoring
Valve and damper monitoring
Service: Air & non aggressive gases
Material: ABS
Electrical Connection: 3 Screw terminal
Cable Entry: M16
Pressure Connection: Male 0 5 MM
Weight: 150 gms
Operation Temperature: -20 to 60° C
Storage Temperature: -40 to 85° C
Maximum Pressure: 50 kPA
IP Protection: IP54
2 Fixing Screws
2 Plastic duct connectors
2 m tube 0 4/7 mm
Metallic duct connectors
- INTRODUCTIONS
- TECHNICAL DATA
- OPTIONAL ACCESSORIES
- MODEL SUMMARY
Model Code |
Pressure range |
Switching difference |
Accuracy of Switching point Low limit typ. |
Electrical rating resistive load |
Accuracy of Switching Point High limit typ. |
Electrical ratind inductive load |
PS4500 |
500...4500 pa |
180 pa |
500 Pa±50 Pa |
4500 Pa±200Pa |
5A/250VAC |
2A/250VAC |